2004-03-09 00:00:00 | 1) BUILDING ADDRESS REQUIRED ON PROPER |
| ELEVATION. |
| |
| 2) IS THE EXISTING APPROVED UNITS |
| UNDER THE SAME OWNERSHIP AS THE NEW |
| PROPOSED BUILDING. |
| |
| 3) THE ELECTRICAL LEGEND DOES NOT |
| IDENTIFY REQUIRED ELECTRIC POWERED |
| SMOKE DETECTORS. ONLY DUCT SMOKE |
| DETECTORS SHOWN ON LEGEND. |
| |
| 4) THE WINDOW SCHEDULE SHALL IDENTIFY |
| ALL EGRESS WINDOWS IN THE REMARKS |
| SECTION. |
| |
| 5) PLANS DO NOT INDICATE INTERIOR |
| FINISH CLASSIFICATION FOR WALLS AND |
| CEILINGS. |
| |
| 6) PLANS DO NOT INDICATE PRESCRIPTIVE |
| STRENGTH REQUIREMENTS FOR METAL |
| STAIR RAILINGS. |
| |
| 7) ALL EGRESS WINDOWS SHALL BE NOTED |
| ON THE ARCHITECTURAL PLANS. |
| |
| 8) PLEASE SHOW ALL TENANT DEMISING |
| WALLS WITH HOURLY RATINGS WITH UL |
| NUMBERS. |
| |
| 9) NO MENTION OF FIRE EXTINGUISHERS. |
| |
| 10) PLEASE INDICATE CONSTRUCTION TYPE |
| ON PLANS, AND OCCUPANT LOADS. |
| |
| 11) PLEASE PROVIDE A LIFE SAFETY PLAN. |
| |
| 12) THE FIRE HYDRANT SHOWN ON C-5 SHALL |
| HAVE 7 1/2 FEET CLEARANCE TO THE FRONT |
| AND SIDES AND 4 FEET TO THE REAR. |
| |
| MIKE CARSILLO, ASSISTANT FIRE MARSHAL |