Plan Review Notes
Plan Review Notes For Permit 04030025
Permit Number 04030025
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-03-09 00:00:001) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 2) IS THE EXISTING APPROVED UNITS
 UNDER THE SAME OWNERSHIP AS THE NEW
 PROPOSED BUILDING.
  
 3) THE ELECTRICAL LEGEND DOES NOT
 IDENTIFY REQUIRED ELECTRIC POWERED
 SMOKE DETECTORS. ONLY DUCT SMOKE
 DETECTORS SHOWN ON LEGEND.
  
 4) THE WINDOW SCHEDULE SHALL IDENTIFY
 ALL EGRESS WINDOWS IN THE REMARKS
 SECTION.
  
 5) PLANS DO NOT INDICATE INTERIOR
 FINISH CLASSIFICATION FOR WALLS AND
 CEILINGS.
  
 6) PLANS DO NOT INDICATE PRESCRIPTIVE
 STRENGTH REQUIREMENTS FOR METAL
 STAIR RAILINGS.
  
 7) ALL EGRESS WINDOWS SHALL BE NOTED
 ON THE ARCHITECTURAL PLANS.
  
 8) PLEASE SHOW ALL TENANT DEMISING
 WALLS WITH HOURLY RATINGS WITH UL
 NUMBERS.
  
 9) NO MENTION OF FIRE EXTINGUISHERS.
  
 10) PLEASE INDICATE CONSTRUCTION TYPE
 ON PLANS, AND OCCUPANT LOADS.
  
 11) PLEASE PROVIDE A LIFE SAFETY PLAN.
  
 12) THE FIRE HYDRANT SHOWN ON C-5 SHALL
 HAVE 7 1/2 FEET CLEARANCE TO THE FRONT
 AND SIDES AND 4 FEET TO THE REAR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910