Plan Review Notes
Plan Review Notes For Permit 04030025
Permit Number 04030025
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-26 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE WIRE SIZE ON THE PANEL SCHEDULE
 FOR THE WATER HEATER IS UNDERSIZED FOR
 THE LOAD SERVED AND THE OCP.
  
 2} INDICATE LOCATION OF WATER HEATER AND
 DICONNECT(CIRCUITS 5&7).
  
 3} THE SMOKE DETECTORS,PER FBC 905.2.1,
 MUST BE INTERCONNECTED, BUT THE PLANS
 INDICATE DIFFERENT CIRCUIT NUMBERS ON
 EACH ONE. PLEASE INDICATE HOW THIS IS
 TO WORK.
  
 4} IN REGARD TO 210.12, SMOKE DETECTORS
 (OR ANY OUTLET), LOCATED IN THE BEDROOM
 MUST BE AFCI PROTECTED. SEE NOTE #3 TO
 CORRELATE.
  
 5} PLEASE PROVIDE DRAWINGS FOR ALL UNIT
 TYPES, INCLUDING THOSE TYPES THAT ARE
 TO BE REVERSED.
  
 6} IF THE INTENT IS TO STACK THE AHU &
 WATER HEATER IN THE SAME CLOSET, PLEASE
 PROVIDE DETAILS OF SAME, INCLUDE
 DISCONNECT LOCATION PER 110.26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026