Plan Review Notes For Permit 04030025 |
Permit Number |
04030025 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-03-26 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE WIRE SIZE ON THE PANEL SCHEDULE | | FOR THE WATER HEATER IS UNDERSIZED FOR | | THE LOAD SERVED AND THE OCP. | | | | 2} INDICATE LOCATION OF WATER HEATER AND | | DICONNECT(CIRCUITS 5&7). | | | | 3} THE SMOKE DETECTORS,PER FBC 905.2.1, | | MUST BE INTERCONNECTED, BUT THE PLANS | | INDICATE DIFFERENT CIRCUIT NUMBERS ON | | EACH ONE. PLEASE INDICATE HOW THIS IS | | TO WORK. | | | | 4} IN REGARD TO 210.12, SMOKE DETECTORS | | (OR ANY OUTLET), LOCATED IN THE BEDROOM | | MUST BE AFCI PROTECTED. SEE NOTE #3 TO | | CORRELATE. | | | | 5} PLEASE PROVIDE DRAWINGS FOR ALL UNIT | | TYPES, INCLUDING THOSE TYPES THAT ARE | | TO BE REVERSED. | | | | 6} IF THE INTENT IS TO STACK THE AHU & | | WATER HEATER IN THE SAME CLOSET, PLEASE | | PROVIDE DETAILS OF SAME, INCLUDE | | DISCONNECT LOCATION PER 110.26. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|