2004-05-20 00:00:00 | ************ UNSAT ***************** |
| |
| 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED PER 210.8A-6 |
| |
| 3) NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| MISSING IN ONE BEDRM |
| |
| 4 ) NOTE: PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| MISSING REAR. |
| |
| 5)NOTE: PLEASE SEE MISSING RECEPT REQ'D |
| FOR A/C EQUIPMENT. 210.63 |
| |
| 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| PANEL SCHEDULE SHOWS RECEPTS ONLY. |
| 2002 NEC 210.12 |
| |
| 7)NOTE: PLEASE SEE OCP SHOWN FOR 10KW |
| HEAT IS AT 50A. PLEASE SEE 424.3B FOR |
| MIN 125%. |
| |
| 8)NOTE: PLEASE SEE PANEL SCHEDULE DOES |
| NOT INCLUDE THE TWO MIN REQ'D SMALL |
| APPLIANCE CIRCUITS. 210.11/ |
| |
| 9)NOTE: PLEASE LOAD CALCULATIONS, LOAD |
| FOR AHU MAY NOT BE DERATED AT 40%. |
| PLEASE SEE 220.32 |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |