Plan Review Notes
Plan Review Notes For Permit 04030011
Permit Number 04030011
Review Stop E
Sequence Number 5
Notes
Date Text
2004-05-20 00:00:00************ UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A-6
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
 MISSING IN ONE BEDRM
  
 4 ) NOTE: PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
 MISSING REAR.
  
 5)NOTE: PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 6 )NOTE: PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
 PANEL SCHEDULE SHOWS RECEPTS ONLY.
 2002 NEC 210.12
  
 7)NOTE: PLEASE SEE OCP SHOWN FOR 10KW
 HEAT IS AT 50A. PLEASE SEE 424.3B FOR
 MIN 125%.
  
 8)NOTE: PLEASE SEE PANEL SCHEDULE DOES
 NOT INCLUDE THE TWO MIN REQ'D SMALL
 APPLIANCE CIRCUITS. 210.11/
  
 9)NOTE: PLEASE LOAD CALCULATIONS, LOAD
 FOR AHU MAY NOT BE DERATED AT 40%.
 PLEASE SEE 220.32
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]