Plan Review Notes
Plan Review Notes For Permit 04030011
Permit Number 04030011
Review Stop E
Sequence Number 4
Notes
Date Text
2004-05-05 00:00:00************* UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT PLANS/DRAWINGS
 WITH MIN ELECTRICAL REQ'D PER NEC 2002
 PANEL SCHEDULE SHOWING MIN CIRCUITS,
 RISER, AND ALL WORK TO BE IN SCOPE.
 PLEASE SEE FBC 104.2.1 FOR MIN PLANS
 REQ'DFOR CLARIFY, BEING COMPLETE AND
 FULLY LEGIBLE.
 PLAN MUST ALSO CONTAIN PRINTED NAME AND
 SIGNATURE OF PERSON RESPONSIBLE FOR
 DRAWING.
 THE PLAN/ DRAWING SUBMITTED IS NOT
 ACCEPTABLE FOR CODE COMPLIANCE, THERE
 ARE ITEMS MISSING FOR MIN CODE COMPLI-
 -ANCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]