Plan Review Notes
Plan Review Notes For Permit 04021150
Permit Number 04021150
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-01 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE COMPUTE LOAD CALCULATIONS PER
 220.3. NOTE THAT DEMAND FACTORS THAT
 WERE TAKEN ARE FOR DWELLING UNITS. SEE
 210.19 FOR CONTINUOUS LOADS'INCLUDING
 220.3(B)(9)' SHOW THAT CALCULATION AS
 WELL.
  
 2} REGARDING THE AIR HANDLERS PLEASE SEE
 220.3(B)(1), @ 100%. THERE IS NO DEMAND
 FACTOR FOR COMMERCIAL A/C.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]