Plan Review Notes
Plan Review Notes For Permit 04021143
Permit Number 04021143
Review Stop E
Sequence Number 1
Notes
Date Text
2004-03-10 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CIRCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 2} THE DOWNSTAIR BEDROOM LABLED #3 (SAME
 AS UPSTAIR #3) NEEDS AN ADDED
 RECEPTACLE PER 210.52(A)(1).
  
 3} THE DISCONNECTS AT THE A/C UNITS DO
 NOT COMPLY WITH 110.26 CLEARANCE
 REQUIREMENTS. PLEASE INDICATE, ON THE
 DRAWING, PLACEMENT FOR COMPLIANCE.
  
 4} PLEASE SEE THE MECHANICAL PLANS TO
 INSURE PLACEMENT OF THE SMOKE DETECTORS
 IS IN COMPLIANCE WITH THE CLEARANCE
 REQUIREMENTS OF NFPA-72, 1999 ED., CH
 #8.
  
 5} NOTE #15 REFERENCES THE 1997 SBC.
 THIS PLAN IS BEING REVIEWED UNDER THE
 2001 FLORIDA BUILDING CODE. ALSO IT
 SHOULD BE NOTED THAT SMOKE DETECTORS IN
 BEDROOMS MUST COMPLY WITH 210.12 AND BE
 ARC FAULT PROTECTED.
  
 6} PLEASE INDICATE THE AMPERAGE RATING
 OF THE FUSE OR BREAKER IN THE MAIN
 DISCONNECT, ALSO THE AIC RATING OF SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026