2004-03-10 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CIRCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED, |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| 2} THE DOWNSTAIR BEDROOM LABLED #3 (SAME |
| AS UPSTAIR #3) NEEDS AN ADDED |
| RECEPTACLE PER 210.52(A)(1). |
| |
| 3} THE DISCONNECTS AT THE A/C UNITS DO |
| NOT COMPLY WITH 110.26 CLEARANCE |
| REQUIREMENTS. PLEASE INDICATE, ON THE |
| DRAWING, PLACEMENT FOR COMPLIANCE. |
| |
| 4} PLEASE SEE THE MECHANICAL PLANS TO |
| INSURE PLACEMENT OF THE SMOKE DETECTORS |
| IS IN COMPLIANCE WITH THE CLEARANCE |
| REQUIREMENTS OF NFPA-72, 1999 ED., CH |
| #8. |
| |
| 5} NOTE #15 REFERENCES THE 1997 SBC. |
| THIS PLAN IS BEING REVIEWED UNDER THE |
| 2001 FLORIDA BUILDING CODE. ALSO IT |
| SHOULD BE NOTED THAT SMOKE DETECTORS IN |
| BEDROOMS MUST COMPLY WITH 210.12 AND BE |
| ARC FAULT PROTECTED. |
| |
| 6} PLEASE INDICATE THE AMPERAGE RATING |
| OF THE FUSE OR BREAKER IN THE MAIN |
| DISCONNECT, ALSO THE AIC RATING OF SAME. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |