Plan Review Notes For Permit 04021067 |
Permit Number |
04021067 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-04-06 00:00:00 | DENIED | | | | 1) THE HORIZONTAL SLIDING WINDOWS IN THE | | BREAKFAST AREA EXCEED THE MAXIMUM HEIGHT | | LISTED IN THE PRODUCT APPROVAL THAT WAS | | SUBMITTED. SUBMIT APPROPRIATE PRODUCT | | APPROVALS. | | | | 2) THE LAWSON PRODUCTS HAVE STATE | | PRODUCT APPROVALS WITH APPROVED STATUS. | | SITE SPECIFIC PRODUCT APPROVALS ARE NO | | LONGER NECESSARY FOR THEM. PLEASE SUBMIT | | THE APPROPRIATE STATE PRODUCT APPROVAL | | COVER SHEET AND CORRESPONDING NOA. | | | | NOTE: THE SITE SPECIFIC PRODUCT APPROVAL | | FORM HAS BEEN REVISED. THE PROJECT | | LOCATION IS REQUIRED. THE CATEGORY OF | | PRODUCT AND APPROVAL METHOD IS REQUIRED | | ON THE FORM. | | | | 3) THE PITTSBURG GLASS BLOCK ALSO HAS | | APPROVED STATE PRODUCT APPROVAL. SUBMIT | | STATE PRODUCT APPROVAL COVER AND NOA. | | | | 4) SUBMIT THE PROPER APPLICATION FOR | | LOCAL PRODUCT APPROVAL FOR THE A&P | | CUSTOM FIXED WINDOWS. IF THE SITE | | SPECIFIC FORM IS USED THE PROJECT | | LOCATION IS REQUIRED TO BE LISTED ON THE | | FORM. SEE NEW FORMS ATTACHED. | | | | 5) STORM PANELS WILL REQUIRE A SEPARATE | | PERMIT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 |
|