2004-05-19 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04021048
 ADD: 3031 OKEECHOBEE BLVD
 CONT: POPPER & ASSOCIATES
 TEL: (561)719-7133
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMMENT# 1 FROM PREVIOUS REVIEW:
 ADDITIONAL INFO ON THE WAYNE DAWSON
 ROLL UP DOOR.
 THE INFORMATION PROVIDED HAS DESCREPAN-
 CIES, THE FIRST SUBITTAL IS FOR OVERHEAD
 GARAGE DOOR(FIRE RATED) SERIES 640 OR
 641. THE SECOND IS A MIAMI-DADE NOA FOR
 A EXTERIOR GARGE DOOR SERIES 610/620,
 THE THIRD IS FOR WAYNE DALSON SERIES
 AKBAR 89. NONE OF THESE SUBMITTALS ACT-
 UALLY SPELL OUT WHAT RATING IS TO BE
 USED. THE COVERSHEET INDICATES A SEPERAT
 ION FROM THE SHOWROOMWITH THE PARTS
 STORAGE. FOR S2 STORAGE A 2 HR WALL AND
 1 1/2 HR OPENING PROTECTIVES REQUIRED.
 SUBMIT THE ACTUAL UNIT TO BE INSTALLED!
  
 THE SECOND ISSUE WITH THIS ISSUE IS THE
 DETAIL-1, THE ROLL DOWN DOOR ASSUMED TO
 BE 1 1/2 HR RATED IS TO SEAL AGAINST THE
 NEW COUNTERTOP, WHICH IS (2) LAYERS OF
 PLYWOOD SEE 709.6.2A,5/8" PLYWOOD IS ASS
 IGNED A TIME OF 15 MIN. EVEN IF WE WENT
 WITH 20 MIN FOR 3/4" TWO LAYERS STILL IS
 GOOD FOR 40 MINUTES?
  
 2) COMMENT "F" FROM PREVIOUS REVIEW DEAL
 S WITH THE EXITING OF THE 2ND FLOOR.
 THE ANSWER WAS , EXITING NOT AFFECTED BY
 THE GOING THROUGH THE FLOOR.
 THE XEROX SUBMITTAL ARE NOT FOR THE
 2ND FLOOR BUT THE FIRST FLOOR. THE AREA
 WHERE THE FLOOR IS CUT AWAY MAY AFFECT
 TRAVEL DISTANCES TO EXITING FOR THE
 SECOND FLOOR THIS IS WHY THE REQUEST WAS
 MADE AND STILL REMAINS A UNANSWERED QUES
 TION?