Plan Review Notes
Plan Review Notes For Permit 04020874
Permit Number 04020874
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-29 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE P.R. NUMBERS ON THE IMPACT FEE
 RECEIPT AND THE PLANS DO NOT MATCH.
 PLEASE SUBMIT CORRECT RECEIPT.
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4)FL. BLD CODE 1606.1.7 THE FOLLOWING
 INFORMATION RELATED TO WIND SHALL BE
 SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
 SPECIFY THE APPLICABLE ENCLOSURE
 CLASSIFICATION AND INTERNAL PRESSURE
 COEFFICENT IF DESIGNING WITH ASCE 7-98.
  
 5) FBC TABLE 1604.1 REQUIRES ATTICS
 WITHOUT STORAGE TO HAVE 10PSF LIVE LOAD.
 SPECIFY THIS ON THE PLANS.
  
 6) THE ENTRY COLUMN DETAIL 10 SHEET 2
 SPECIFIES 3- #4BARS E.W. AND THE
 FOUNDATION PLAN SPECIFIES 4- #5 BARS.
 PLEASE CLARIFY.
  
 7) DETAIL 3 ON 5 HAS A CONNECTION DETAIL
 THAT IS ILLEGIBLE DUE TO PRINTING ERROR.
  
 8) THE REINFORCMENT NOTE FOR THE BEAM
 OVER THE SLIDING GLASS DOOR IN THE
 MASTER SUITE IS ILLEGIBLE.
  
 9) THE DIMENSIONS LISTED FOR THE BUTT
 GLASS DIFFER ON SHEETS 5 AND 7. PLEASE
 CORRECT.
  
 10) ADD NOTES TO THE TRUSS FRAMING PLAN
 ON SHEET 9 TO CLARIFY THAT THE #4
 CONNECTOR IS FOR THE FLOOR TRUSSES AND
 THE (2) #7 CONNECTORS AT THE RIGHT SIDE
 OF THE LAYOUT ARE FOR ANCHORING THE
 TRUSSES TO THE POSTS BELOW.
  
 11) THE NUE-VUE NVTA 48 CONNECTOR ON 5
 AND THE NVSTA 48 ON 9, DO NOT MATCH THE
 FLORIDA PRODUCE APPROVAL THAT WAS
 SUBMITTED. PLEASE CORRECT.
  
 12) THE TRUSS ANCHOR SCHEDULE LISTS A
 SIMPSON HUC 412 CONNECTOR WITH 1505#
 UPLIFT AND FL. PRODUCT APPROVAL THAT WAS
 SUBMITTED IS FOR HU 412 WITH 905# UPLIFT
 PLEASE CORRECT.
  
 13) THE FLORIDA PRODUCT APPROVAL FOR THE
 COLLIER GARAGE DOOR (FL 1269) IS
 PENDING. SUBMIT APPROPRIATE PRODUCT
 APPROVAL.
  
 14) THE INSTALLATION DRAWINGS FOR THE
 COLLIER GARAGE DOOR IS LIMITED TO A
 MINIMUM SIZE OF 10'X 6' (60 SQFT) AND
 THE DOOR ON THE PLANS IS SMALLER AT
 8'X 7' (56 SQFT). SUBMIT STATE OR LOCAL
 PRODUCT APPROVAL FOR THE SMALL GARAGE
 DOOR.
  
 15) SUBMIT STATE OR LOCAL PRODUCT
 APPROVAL FOR THE BUTT GLASS WINDOW AND
 STOREFRONT SYSTEM.
  
 16) SUBMIT STATE OR LOCAL PRODUCT
 APPROVALS, KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved