Date |
Text |
2004-03-29 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) THE P.R. NUMBERS ON THE IMPACT FEE |
| RECEIPT AND THE PLANS DO NOT MATCH. |
| PLEASE SUBMIT CORRECT RECEIPT. |
| |
| 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4)FL. BLD CODE 1606.1.7 THE FOLLOWING |
| INFORMATION RELATED TO WIND SHALL BE |
| SHOWN ON THE CONSTRUCTION DRAWINGS, |
| 1)- BASIC WIND SPEED, MPH |
| 2)- WIND IMPORTANCE FACTOR, & BUILDING |
| CATEGORY |
| 3)- WIND EXPOSURE |
| 4)- INTERNAL PRESSURE COEFFICIENT, |
| 5)- COMPONENTS & CLADDING, THE DESIGN |
| WIND PRESSURES IN TERMS OF PSF. |
| SPECIFY THE APPLICABLE ENCLOSURE |
| CLASSIFICATION AND INTERNAL PRESSURE |
| COEFFICENT IF DESIGNING WITH ASCE 7-98. |
| |
| 5) FBC TABLE 1604.1 REQUIRES ATTICS |
| WITHOUT STORAGE TO HAVE 10PSF LIVE LOAD. |
| SPECIFY THIS ON THE PLANS. |
| |
| 6) THE ENTRY COLUMN DETAIL 10 SHEET 2 |
| SPECIFIES 3- #4BARS E.W. AND THE |
| FOUNDATION PLAN SPECIFIES 4- #5 BARS. |
| PLEASE CLARIFY. |
| |
| 7) DETAIL 3 ON 5 HAS A CONNECTION DETAIL |
| THAT IS ILLEGIBLE DUE TO PRINTING ERROR. |
| |
| 8) THE REINFORCMENT NOTE FOR THE BEAM |
| OVER THE SLIDING GLASS DOOR IN THE |
| MASTER SUITE IS ILLEGIBLE. |
| |
| 9) THE DIMENSIONS LISTED FOR THE BUTT |
| GLASS DIFFER ON SHEETS 5 AND 7. PLEASE |
| CORRECT. |
| |
| 10) ADD NOTES TO THE TRUSS FRAMING PLAN |
| ON SHEET 9 TO CLARIFY THAT THE #4 |
| CONNECTOR IS FOR THE FLOOR TRUSSES AND |
| THE (2) #7 CONNECTORS AT THE RIGHT SIDE |
| OF THE LAYOUT ARE FOR ANCHORING THE |
| TRUSSES TO THE POSTS BELOW. |
| |
| 11) THE NUE-VUE NVTA 48 CONNECTOR ON 5 |
| AND THE NVSTA 48 ON 9, DO NOT MATCH THE |
| FLORIDA PRODUCE APPROVAL THAT WAS |
| SUBMITTED. PLEASE CORRECT. |
| |
| 12) THE TRUSS ANCHOR SCHEDULE LISTS A |
| SIMPSON HUC 412 CONNECTOR WITH 1505# |
| UPLIFT AND FL. PRODUCT APPROVAL THAT WAS |
| SUBMITTED IS FOR HU 412 WITH 905# UPLIFT |
| PLEASE CORRECT. |
| |
| 13) THE FLORIDA PRODUCT APPROVAL FOR THE |
| COLLIER GARAGE DOOR (FL 1269) IS |
| PENDING. SUBMIT APPROPRIATE PRODUCT |
| APPROVAL. |
| |
| 14) THE INSTALLATION DRAWINGS FOR THE |
| COLLIER GARAGE DOOR IS LIMITED TO A |
| MINIMUM SIZE OF 10'X 6' (60 SQFT) AND |
| THE DOOR ON THE PLANS IS SMALLER AT |
| 8'X 7' (56 SQFT). SUBMIT STATE OR LOCAL |
| PRODUCT APPROVAL FOR THE SMALL GARAGE |
| DOOR. |
| |
| 15) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVAL FOR THE BUTT GLASS WINDOW AND |
| STOREFRONT SYSTEM. |
| |
| 16) SUBMIT STATE OR LOCAL PRODUCT |
| APPROVALS, KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |