2004-04-09 00:00:00 | |
| PROVISO |
| ~~~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| THIS PROVISO IS BEING ISSUED TO ALLOW |
| THE ELECTRICAL WORK TO BEGIN WITHOUT |
| DELAY. THERE ARE THE FOLLOWING ISSUES |
| HOWEVER,THAT NEED TO BE ADDRESSED PRIOR |
| TO ROUGH INSPECTION. |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW AS A REVISION TO THIS PERMIT. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| RATED FOR THE AVAILABLE FAULT CURRENT. |
| PER 110.9/215.5 |
| |
| 2} PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 3} PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5. SUBMIT COUNTER LOCA |
| TION PLAN ON THE DRAWING TO BE REVIEWED |
| FOR COMPLIANCE. SEE 210.8(A)(6) ALSO. |
| |
| 4} PLEASE LIST ALL THE REQ'D |
| DEDICATED BATH(S) CIRCUIT(S) ON PANEL |
| SCHEDULE. PER 210.52D, 210.11C3 |
| |
| 5} PLEASE SHOW OUTLET SPACING PER |
| 210.52. 2',6`,12`. SEE REDLINED PLANS, |
| REDRAW PER ACTUAL LOCATIONS. |
| |
| 6} SEE NFPA-72, 1999 EDITION FOR SMOKE D |
| ETECTOR LOCATION. (3' FROM BATH DOORS). |
| |
| 7} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |