Plan Review Notes
Plan Review Notes For Permit 04020849
Permit Number 04020849
Review Stop E
Sequence Number 2
Notes
Date Text
2004-04-09 00:00:00 
 PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THIS PROVISO IS BEING ISSUED TO ALLOW
 THE ELECTRICAL WORK TO BEGIN WITHOUT
 DELAY. THERE ARE THE FOLLOWING ISSUES
 HOWEVER,THAT NEED TO BE ADDRESSED PRIOR
 TO ROUGH INSPECTION.
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW AS A REVISION TO THIS PERMIT.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 3} PLEASE SEE RECEPTS SERVING
 KITCHEN COUNTERSPACE TO MEET 210.52C-
 SEC'S 1,2,3,4 AND 5. SUBMIT COUNTER LOCA
 TION PLAN ON THE DRAWING TO BE REVIEWED
 FOR COMPLIANCE. SEE 210.8(A)(6) ALSO.
  
 4} PLEASE LIST ALL THE REQ'D
 DEDICATED BATH(S) CIRCUIT(S) ON PANEL
 SCHEDULE. PER 210.52D, 210.11C3
  
 5} PLEASE SHOW OUTLET SPACING PER
 210.52. 2',6`,12`. SEE REDLINED PLANS,
 REDRAW PER ACTUAL LOCATIONS.
  
 6} SEE NFPA-72, 1999 EDITION FOR SMOKE D
 ETECTOR LOCATION. (3' FROM BATH DOORS).
  
 7} PLEASE LIST THE REQ'D ARC
 FAULT PROTECTED CURCUIT(S) ON PANEL
 SCHEDULE. PLEASE SEE THAT ALL "OUTLETS"
 IN BEDROOMS ARE TO BE PROTECTED ,
 INCLUDING, LTS, RECEPTS, SD'S ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026