2004-12-01 00:00:00 | |
| PROVIS0 |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW PRIOR TO ROUGH INSPECTION. |
| |
| 1} PLEASE SEE THAT A #2 EQUIPMENT |
| GROUND IS SHOWN BEING RAN WITH THE |
| FEEDERS TO THE PANELS FROMTHE |
| DISCONNECTS.VERIFY THE SIZE OF SAME. A |
| #6 IS REQUIRED PER 250.122. |
| |
| 2} THE #2 EQUIPMENT GROUND RUNNING |
| BETWEEN DISCONNECTS IS IN VIOLATION OF |
| 250.6(B) AND MUST NOT BE INSTALLED. |
| |
| 3} THERE IS A POOL PUMP SHOWN ON THE |
| DRAWINGS BUT NONE LISTED IN THE |
| CALCULATIONS.ALSO IF THE POOL IS TO BE |
| HEATED PLEASE SHOW THAT CALCULATION. |
| |
| 4} AIR HANDLER #2 IS SHOWN ON THE |
| CALCULATIONS @ 7.5 KW AND LISTED ON THE |
| MECHANICAL PLANS AS 10KW. PLEASE |
| CORRELATE. |
| |
| 5} THE LOAD CALCULATIONS MUST CONTAIN A |
| CALCULATION FOR THE DRYER PER 220.18. |
| |
| 6} PLEASE SHOW THE RECEPTACLE LOCATION |
| FOR THE "WHIRL-TUB" AND SHOW GFI |
| COMPLIANCE PER 680.62(A). |
| |
| 7} RECEPTACLES NEED TO BE ADDED |
| TO BEDROOM #4 TO COMPLY WITH |
| 210.52(A)(2). |
| |
| ONE SET OF REVIEWED PLANS ARE MARKED TO |
| INDICATE THE AREAS OF COMMENTS.PLEASE |
| SEE THIS SET AND CALL IF THERE ARE ANY |
| QUESTIONS. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |