Plan Review Notes
Plan Review Notes For Permit 04020827
Permit Number 04020827
Review Stop E
Sequence Number 4
Notes
Date Text
2004-12-01 00:00:00 
 PROVIS0
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW PRIOR TO ROUGH INSPECTION.
  
 1} PLEASE SEE THAT A #2 EQUIPMENT
 GROUND IS SHOWN BEING RAN WITH THE
 FEEDERS TO THE PANELS FROMTHE
 DISCONNECTS.VERIFY THE SIZE OF SAME. A
 #6 IS REQUIRED PER 250.122.
  
 2} THE #2 EQUIPMENT GROUND RUNNING
 BETWEEN DISCONNECTS IS IN VIOLATION OF
 250.6(B) AND MUST NOT BE INSTALLED.
  
 3} THERE IS A POOL PUMP SHOWN ON THE
 DRAWINGS BUT NONE LISTED IN THE
 CALCULATIONS.ALSO IF THE POOL IS TO BE
 HEATED PLEASE SHOW THAT CALCULATION.
  
 4} AIR HANDLER #2 IS SHOWN ON THE
 CALCULATIONS @ 7.5 KW AND LISTED ON THE
 MECHANICAL PLANS AS 10KW. PLEASE
 CORRELATE.
  
 5} THE LOAD CALCULATIONS MUST CONTAIN A
 CALCULATION FOR THE DRYER PER 220.18.
  
 6} PLEASE SHOW THE RECEPTACLE LOCATION
 FOR THE "WHIRL-TUB" AND SHOW GFI
 COMPLIANCE PER 680.62(A).
  
 7} RECEPTACLES NEED TO BE ADDED
 TO BEDROOM #4 TO COMPLY WITH
 210.52(A)(2).
  
 ONE SET OF REVIEWED PLANS ARE MARKED TO
 INDICATE THE AREAS OF COMMENTS.PLEASE
 SEE THIS SET AND CALL IF THERE ARE ANY
 QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW