Plan Review Notes For Permit 04020827 |
Permit Number |
04020827 |
|
Review Stop |
B |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-11-05 00:00:00 | BUILDING PROVISO: | | 1-DRAWING A1: ARCHITECT SPECIFIES 2X | | MULLION. PROVIDE PRODUCT APPROVAL FOR | | THIS SIZE MULLION. | | AND, CLEARLY INDICATE FASTENERS AND | | ATTACHMENT OF DOORS AND WINDOWS TO THIS | | STRUCTURAL MULLION. SEC. 104.2.1.2 CITY | | AMENDMENTS TO FBC 2001. | | | | 2-PROVIDE PRODUCT APPROVAL FOR ENTRY | | DOORS WITH MISSILE IMPACT GLAZING AS | | SPECIFIED ON ARCHITECTURAL PLANS. | | | | 3-PROVIDE COMPLETE SECTIONS AND DETAILS | | OF FRAMING AT ENTRY PORCH THAT MATCH | | ROOF FRAMING PLANS. SPECIFY ALL | | FASTENERS, SPECIALLY AT THE ENDS. | | CLARIFY HOW ARE BOTTOM 2X12'S ATTACHED | | TO STEEL COLUMN AND TO MASONRY. SECTION | | 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
|