Date |
Text |
2004-03-02 00:00:00 | |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SEE THAT A #2 EQUIPMENT |
| GROUND |
| IS SHOWN BEING RAN WITH THE FEEDERS TO |
| THE PANELS FROMTHE DISCONNECTS.VERIFY |
| THE SIZE OF SAME. A # 6 IS REQUIRED PER |
| 250.122. |
| |
| 2} THE #2 EQUIPMENT GROUND RUNNING |
| BETWEEN DISCONNECTS IS IN VIOLATION OF |
| 250.6(B) AND MUST NOT BE INSTALLED. |
| |
| 3} THE LAUNDRY CIRCUIT MUST BE |
| CALCULATED AT 1500 VA PER 220.16(B) |
| |
| 4} THERE IS A POOL PUMP SHOWN ON THE |
| DRAWINGS BUT NONE LISTED IN THE |
| CALCULATIONS.ALSO IF THE POOL IS TO BE |
| HEATED PLEASE SHOW THAT CALCULATION. |
| |
| 5} AIR HANDLER #2 IS SHOWN ON THE |
| CALCULATIONS @ 7.5 KW AND LISTED ON THE |
| MECHANICAL PLANS AS 10KW. PLEASE |
| CORRELATE. |
| |
| 6} THE LOAD CALCULATIONS MUST CONTAIN A |
| CALCULATION FOR THE DRYER PER 220.18. |
| |
| 7} PLEASE ADD A RECEPTACLE AT THE FRONT |
| OF THE HOUSE PER 220.52(E). |
| |
| 8} PLEASE SHOW THE RECEPTACLE LOCATION |
| FOR THE "WHIRL-TUB" AND SHOW GFI |
| COMPLIANCE PER 680.62(A). |
| |
| 9} RECEPTACLES NEED TO BE ADDED |
| TO BEDROOMS #3 & #4 TO COMPLY WITH |
| 210.52(A)(2). |
| |
| ONE SET OF REVIEWED PLANS ARE MARKED TO |
| INDICATE THE AREAS OF COMMENTS.PLEASE |
| SEE THIS SET AND CALL IF THERE ARE ANY |
| QUESTIONS. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |