 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SEE THAT A #2 EQUIPMENT
 GROUND
 IS SHOWN BEING RAN WITH THE FEEDERS TO
 THE PANELS FROMTHE DISCONNECTS.VERIFY
 THE SIZE OF SAME. A # 6 IS REQUIRED PER
 250.122.
  
 2} THE #2 EQUIPMENT GROUND RUNNING
 BETWEEN DISCONNECTS IS IN VIOLATION OF
 250.6(B) AND MUST NOT BE INSTALLED.
  
 3} THE LAUNDRY CIRCUIT MUST BE
 CALCULATED AT 1500 VA PER 220.16(B)
  
 4} THERE IS A POOL PUMP SHOWN ON THE
 DRAWINGS BUT NONE LISTED IN THE
 CALCULATIONS.ALSO IF THE POOL IS TO BE
 HEATED PLEASE SHOW THAT CALCULATION.
  
 5} AIR HANDLER #2 IS SHOWN ON THE
 CALCULATIONS @ 7.5 KW AND LISTED ON THE
 MECHANICAL PLANS AS 10KW. PLEASE
 CORRELATE.
  
 6} THE LOAD CALCULATIONS MUST CONTAIN A
 CALCULATION FOR THE DRYER PER 220.18.
  
 7} PLEASE ADD A RECEPTACLE AT THE FRONT
 OF THE HOUSE PER 220.52(E).
  
 8} PLEASE SHOW THE RECEPTACLE LOCATION
 FOR THE "WHIRL-TUB" AND SHOW GFI
 COMPLIANCE PER 680.62(A).
  
 9} RECEPTACLES NEED TO BE ADDED
 TO BEDROOMS #3 & #4 TO COMPLY WITH
 210.52(A)(2).
  
 ONE SET OF REVIEWED PLANS ARE MARKED TO
 INDICATE THE AREAS OF COMMENTS.PLEASE
 SEE THIS SET AND CALL IF THERE ARE ANY
 QUESTIONS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026