Plan Review Notes
Plan Review Notes For Permit 04020772
Permit Number 04020772
Review Stop E
Sequence Number 2
Notes
Date Text
2004-12-15 00:00:00 
  
 THE RECEPTACLES REDLINED ON THE
 REVIEWED
 SET OF PLANS TO COMPLY WITH 210.52 DO
 NOT APPEAR TO HAVE BEEN INSTALLED. SEE
 HIGHLIGHTED AREAS ON THE PLANS BEING
 RETURNED.
  
 THE SMOKE DETECTOR THAT WAS RELOCATED TO
 THE FOYER FROM THE HALL OUTSIDE BEDROOM
 #2 DOES NOT MEET THE INTENT OF NFPA-72,
 8-1.4.1.6.2 "IMMEDIATE VICINITY"
 ESPECIALLY GIVEN THE FACT OF THE DOOR
 THAT COULD CLOSE THE HALL OFF FROM THE
 DETECTOR.
  
 THE PLANS MUST BE REVISED BY THE
 DESIGNER OF RECORD AND THAT PERSONS NAME
 PRINTED AND SIGNED ON THE
 PAGE(S).HANDDRAWN CHANGES WILL NOT BE
 ACCEPTED PER 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026