Plan Review Notes
Plan Review Notes For Permit 04020698
Permit Number 04020698
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-23 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS ARE SEALED
 COPIES AND DO NOT CONTAIN ORIGINAL
 SIGNATURE. PLEASE SEE FS 481.221
  
  
 2)NOTE: PLEASE SEE PLANS CAME IN W/OUT
 FEE BEING PAID. PLEASE VERIFY IF THESE
 ARE RE-STAMPS OR REVISIONS?
 PLANS DO NOT CONATIN ANY REV'S FROM
 LAST REVIEWED SET?
  
 3 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 PLEASE SEE BZ ATTACHED. FEE TO BE PAID
 BEFORE PICKING UP.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]