Plan Review Notes
Plan Review Notes For Permit 04020656
Permit Number 04020656
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020656
 ADD: 310 EVERNIA ST
 CONT: ANDERON MOORE
 TEL: (561) 662-1819
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 A) PLANS DO NOT INDICATE THE SPACING OF
 THE METAL TRUSSES APPROX 5'-6" TO
 6'-0" WHAT TYPE OF SYSTEM WILL ACT
 AS INTERMEDIATE FRAMING?
 B) PLAN ALSO ARE MISSING WHAT TYPE OF
 SHEATHING WILL BE USED FOR THE ROOF
 DECK. TYPE IV BLDG. SEE TABLE 600
 (FOOTNOTE "E").
 C) PLANS INDICATE BOTH THE USE OF BAR
 JOIST AS WELL AS METAL ROOF TRUSSES?
 D) THE BAR JOIST DO NOT GIVE THE CENTER
 TO CENTER DIMENSION?
 E) PLANS DO NOT INDICATE HOW THE WIRE
 LATH WILL BE ATTACHED NOR THE SPACING
 OF THE FRAMING MEMBERS?
 F) PLANS DO NOT GIVE THE MAGNITUDE OF
 LOADS TO BE RESISTED, VERTICAL,
 HORIZONTAL NOR GRAVITY, PART OF THE
 MAIN WIND-FORCE RESISTING SYSTEM.
 G) INDICATE IF THIS STRUCTURE WAS DESIGN
 ED AS OPEN?
  
 2) AUTOMATIC TELLAR MACHINES 11-4.34
 SEE SUBSECTION 1-5.
  
 3) PROVIDE NOC RECORDED WITH THE CLERK
 OF COURT BEFORE A PERMIT CAN BE ISSUED.
  
 4) FL BLD CODE 1804.2.2 QUESTIONABLE
 SOILS, WHERE THE BEARING CAPACITY IS
 NOT DEFINETLY KNOWN OR IS IN QUESTION.
 WHERE THE BEARING CAPACITY OF THE SOIL I
 S NOT DEFINITEY KNOWN, OR IS IN QUESTION
 THE BUILDING OFFICIAL MAY REQUIRE EXPLOR
 ATIONS, TEST OR OTHER ADEQUATE PROOF AS
 TO THE PERMISSIBLE SAFE BEARING
 CAPACITY. REQUIRED TEST AND RECOMMENDA-
 TIONS SUBMITTED TO VERIFY BEARING CAPA-
 CITY SHALL BE CERTIFIED BY A GEOTECH-
 NICALREPORT FROM A DESIGN PROFESSIONAL P
 ROPERLY LICENSED IN THE STATE OF
 FLORIDA.
  
 5) BEFORE A PERMIT TO CONSTRUCT CAN BE
 ISSUED, IMPACT FEES MUST BE PAID TO PALM
 BEACH CO.,THE PERMIT PLANS STAMPED BY
 THEM AND THE RECEIPT ATTACHED TO THE
 PERMIT APPLICATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026