Plan Review Notes
Plan Review Notes For Permit 04020477
Permit Number 04020477
Review Stop E
Sequence Number 2
Notes
Date Text
2004-06-17 00:00:00********* UNSAT ***********
  
 1)NOTE: PLEASE SEE ONLY ONE COPY OF
 SHEET E-1E WAS SUBMITTED.
  
 2)NOTE: PLEASE SEE GFI IN MASTER BATH
 IS REQUIRED TO WITHIN 3' OF SINK.
 210.52D
 PLEASE SEE THIS IS THE FIRST SET OF FULL
 SIZE PLANS THAT CORRELATE W/ SCALE.
  
 3)NOTE: PLEASE SEE SD'S ARE BEING SHOWN
 ON TWO SEPARATE CIRCUITS, YET THESE ARE
 REQUIRED TO BE WIRED "INLINE". THIS IS
 NOT POSSIBLE WITH TWO CIRCUITS GOING TO
 THE SAME DEVICES. NFPA-72
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]