Plan Review Notes For Permit 04020367 |
Permit Number |
04020367 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-13 00:00:00 | 1) ELECTRICAL PLANS DO NOT DIPLAY | | ANY EXISTING OR NEW EXIT SIGNS. | | | | 2) PLANS DO NOT INDICATE THAT THE | | EXISTING 3068 DOORS FROM THE EXISTING | | CORRDIOR ARE FIRE RATED AND ARE | | EQUIPPED WITH SELF-CLOSING DEVICES. | | | | 3) ARE THERE ANY NEW OR EXISTING | | FIRE ALARM EQUIPMENT LOCATED WITHIN | | THE SPACE. | | | | 4) PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|