2004-02-19 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE FIRE REVIEW COMMENTS
 AS THEY WILL HAVE AN AFFECT ON ELEC-
 -TRICAL PLANS.
  
 2)NOTE: PLEASE SHOW ALL CIRCUITING ON
 PLANS AND CORRELATE WITH SUBMITTED
 PANEL SCHEDULE.
 PLEASE SEE 700.12 FOR CIRCUITING OF
 EM/EXT LTS.
  
 3)NOTE: PLEASE VERIFY OCP SHOWN FOR
 AHU @5KW. MIN OCP IS 125% PER 424.3B
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  