2004-03-06 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020367
 ADD: 2151 45TH ST# 209
 CONT: MIKE MOORE CONST
 TEL: (561)262-6605
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE A COMPLETE FLOORPLAN
 TO SEE IF THE 2 EXISTS PROVIDED MEET
 THE 1/2 THE DIAGONAL FOR EXISTING. IS
 THE BUILDING FIRESPRINKLERED?
  
 2) PROVIDE ADD INFO FOR THE (2) EGRESS
 DOORS, ARE THEY FIRE RATED AND DO THEY
 HAVE CLOSERS?
  
 3) TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION
 BASED ON INTERIOR FINISH REQUIREMENTS
 BASED ON OCCUPANCY.
  
 4) THE BREAK ROOM SINK MUST MEET THE
 FL ACCESSIBILITY CODE 11-4.24 (1-7)
  
 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026