Plan Review Notes For Permit 04020363 |
Permit Number |
04020363 |
|
Review Stop |
FIRE |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2004-05-11 00:00:00 | ********PROVISO************************* | | 1) THE LETTER DATED APRIL 28, 2004 IN | | RESPONSE TO PLAN REVIEW COMMENTS FOR | | PERMIT #04020363 DID NOT ADDRESS THE | | PREVIOUS PLAN REVIEW COMMENTS BY FIRE. | | | | 2) PLEASE MAKE THE FOLLOWING CORRECTIONS | | TO NOTE #17 AND #19 ON SHEET FA0.1. | | | | * NOTE #17 HVAC DUCT SMOKE DETECTOR | | SHALL BE CONNECTED TO THE FIRE ALARM | | CONTROL PANEL AND SHALL INTIATE A | | GENERAL FIRE ALARM. | | | | * NOTE #19 ALL FIRE ALARM CIRCUITS SHALL | | BE CLASS"A" OR FULLY ADDRESSABLE. | | | | 3) ALL NEW RAMPS AND STAIRS SHALL BE | | PROVIDED WITH HANDRAILS ON BOTH SIDES. | | | | 4) FIRE SPRINKLER DRAWINGS ARE TO BE | | SUBMITTED UNDER SEPARATE COVER AND UNDER | | SEPARATE PERMIT APPLICATION. | | | | | | NATE MCCRAY, CAPTAIN | | 805-6722 OR 835-2910 |
|