2004-05-11 00:00:00********PROVISO*************************
 1) THE LETTER DATED APRIL 28, 2004 IN
 RESPONSE TO PLAN REVIEW COMMENTS FOR
 PERMIT #04020363 DID NOT ADDRESS THE
 PREVIOUS PLAN REVIEW COMMENTS BY FIRE.
  
 2) PLEASE MAKE THE FOLLOWING CORRECTIONS
 TO NOTE #17 AND #19 ON SHEET FA0.1.
  
 * NOTE #17 HVAC DUCT SMOKE DETECTOR
 SHALL BE CONNECTED TO THE FIRE ALARM
 CONTROL PANEL AND SHALL INTIATE A
 GENERAL FIRE ALARM.
  
 * NOTE #19 ALL FIRE ALARM CIRCUITS SHALL
 BE CLASS"A" OR FULLY ADDRESSABLE.
  
 3) ALL NEW RAMPS AND STAIRS SHALL BE
 PROVIDED WITH HANDRAILS ON BOTH SIDES.
  
 4) FIRE SPRINKLER DRAWINGS ARE TO BE
 SUBMITTED UNDER SEPARATE COVER AND UNDER
 SEPARATE PERMIT APPLICATION.
  
  