Plan Review Notes
Plan Review Notes For Permit 04020363
Permit Number 04020363
Review Stop P
Sequence Number 2
Notes
Date Text
2004-04-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 A) SOME COMMENTS FROM PREVIOUS REVIEW
 HAVE NOT BEEN ADDRESS, OR OTHER COMMENTS
 HAVE BEEN RAISED DUE TO COMMENT RESPONSE
 THE NUMBERS FROM THE FIRST REVIEW WILL
 BE USED TO AVOID CONFUSION.
 5) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO THE BLDG. SECTION 608.13.2.
 NO RESPONSE OR BACKFLOW NOTED.
 7) SHT P0.1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED. 607.3.2 -
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 USE, DELETE FROM DETAIL. (SEE PLUMBING
 NOTE 14). - NO RESPONSE NOTED.
 8) SHT P0.1 WATER HEATER DETAIL, PROVIDE
 INFORMATION FROM ENGINEER TO SHOW THAT
 POINT LOADING OF WATER HEATER ON BOTTOM
 CORD OF JOISTS HAS BEEN ADDRESSED. SEC
 1603.3. (APPROX. 300 LBS).
 11) SUBMIT A STORM RISER DIAGRAM. SHT
 P4.1 STORM RISER DIAGRAM SHOWS 8" S.D.
 (10,500 SQ FT) TO CATCH BASIN. MAXIMUM
 10,222 @ 1/8" PER FT SLOPE. EITHER 10"
 PIPE IS REQUIRED OR SHOW SLOPE OF PIPE
 GREATER THAN 1/8" PER FT. - THIS IS A
 NEW COMMENT DUE TO RESPONSE TO ORIGINAL
 COMMENT.
 12) SHT P-4.1 ROOF PIPING SUPPORT DETAIL
 FOR CONDENSATE. IS THE CONCRETE STEPPING
 STONES ON THE ROOF AN ENGINEERED SYSTEM
 THAT WILL WITHSTAND 140 MPG WIND SPEED?
 INDICATE HOW STONES WILL BE ATTACHED TO
 THE ROOF. INDICATE HOW SLOPE WILL BE
 MAINTAINED FROM ROOF UNITS TO ROOF DRAIN
 RESPONSE NOTED WAS TO ELEMINATE THE DE-
 TAIL. SUBMIT A NEW DETAIL AND ADDRESS
 COMMENTS FROM PREVIOUS REVIEW.
 13) SHT P-4.1 ROOF PIPING SUPPORT DETAIL
 FOR CONDENASATE. DETAIL INDICATES STONES
 TO BE 6'0" ON CENTER. TABLE 308.5 STAES
 4'0" MAX FOR PVC PIPE HORZONTAL SPACING.
 PLEASE CLAIRFY. - RESPONSE WAS TO DELETE
 THE DETAIL. SUBMIT A DETAIL SHOWING HOW
 THE CONDENSATE PIPING WILL BE INSTALLED.
 *********WHEN RESUBMITTING PLANS********
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 ******SEE ATTACHED SHEET CONCERNING*****
 FS 533.80(2)(B) FOR ARCHITECTS & ENGIN-
 EERS.
  