2004-04-05 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| |
| A) SOME COMMENTS FROM PREVIOUS REVIEW |
| HAVE NOT BEEN ADDRESS, OR OTHER COMMENTS |
| HAVE BEEN RAISED DUE TO COMMENT RESPONSE |
| THE NUMBERS FROM THE FIRST REVIEW WILL |
| BE USED TO AVOID CONFUSION. |
| 5) AN RPZ BACKFLOW IS REQUIRED ON WATER |
| SERVICE TO THE BLDG. SECTION 608.13.2. |
| NO RESPONSE OR BACKFLOW NOTED. |
| 7) SHT P0.1 WATER HEATER DETAIL, THERMAL |
| EXPANSION CONTROL IS REQUIRED. 607.3.2 - |
| DIELECTRIC UNIONS NOT APPROVED FOR WATER |
| USE, DELETE FROM DETAIL. (SEE PLUMBING |
| NOTE 14). - NO RESPONSE NOTED. |
| 8) SHT P0.1 WATER HEATER DETAIL, PROVIDE |
| INFORMATION FROM ENGINEER TO SHOW THAT |
| POINT LOADING OF WATER HEATER ON BOTTOM |
| CORD OF JOISTS HAS BEEN ADDRESSED. SEC |
| 1603.3. (APPROX. 300 LBS). |
| 11) SUBMIT A STORM RISER DIAGRAM. SHT |
| P4.1 STORM RISER DIAGRAM SHOWS 8" S.D. |
| (10,500 SQ FT) TO CATCH BASIN. MAXIMUM |
| 10,222 @ 1/8" PER FT SLOPE. EITHER 10" |
| PIPE IS REQUIRED OR SHOW SLOPE OF PIPE |
| GREATER THAN 1/8" PER FT. - THIS IS A |
| NEW COMMENT DUE TO RESPONSE TO ORIGINAL |
| COMMENT. |
| 12) SHT P-4.1 ROOF PIPING SUPPORT DETAIL |
| FOR CONDENSATE. IS THE CONCRETE STEPPING |
| STONES ON THE ROOF AN ENGINEERED SYSTEM |
| THAT WILL WITHSTAND 140 MPG WIND SPEED? |
| INDICATE HOW STONES WILL BE ATTACHED TO |
| THE ROOF. INDICATE HOW SLOPE WILL BE |
| MAINTAINED FROM ROOF UNITS TO ROOF DRAIN |
| RESPONSE NOTED WAS TO ELEMINATE THE DE- |
| TAIL. SUBMIT A NEW DETAIL AND ADDRESS |
| COMMENTS FROM PREVIOUS REVIEW. |
| 13) SHT P-4.1 ROOF PIPING SUPPORT DETAIL |
| FOR CONDENASATE. DETAIL INDICATES STONES |
| TO BE 6'0" ON CENTER. TABLE 308.5 STAES |
| 4'0" MAX FOR PVC PIPE HORZONTAL SPACING. |
| PLEASE CLAIRFY. - RESPONSE WAS TO DELETE |
| THE DETAIL. SUBMIT A DETAIL SHOWING HOW |
| THE CONDENSATE PIPING WILL BE INSTALLED. |
| *********WHEN RESUBMITTING PLANS******** |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| ******SEE ATTACHED SHEET CONCERNING***** |
| FS 533.80(2)(B) FOR ARCHITECTS & ENGIN- |
| EERS. |
| |