Plan Review Notes
Plan Review Notes For Permit 04020363
Permit Number 04020363
Review Stop P
Sequence Number 1
Notes
Date Text
2004-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 11
  
 1) ORIGINAL PERMIT APPLICATION REQUIRED.
 COPIES OF SIGNATURES, NOTARY SEAL ECT
 NOT ACCEPTABLE.
 2) SHOW CLEAR FLOOR SPACE FOR ALL
 ACCESSIBLE FIXTURES PER 11-4.15.5, 11-4.
 16.2, 11-4.18.3, 11-4.19.3, 11-4.22.3,
 AND 11-4.24.5.
 3) SHOW URINAL HEIGHT PER 11-4.18.2.
 (SEE 11-4.22.5).
 4) SHOW LOUNGE, #107 DETAIL #7 SHT A-7.1
 KNEE CLEARANCE 11-4.24.3, DEPTH 11-4.24.
 4, & EXPOSED PIPES & SURFACES 11-4.24.6.
 5) AN RPZ BACKFLOW IS REQUIRED ON WATER
 SERVICE TO BLDG. 608.13.2
 6) INFORMATIONAL - SEPARATE IRRIGATION
 PERMIT IS REQUIRED.
 7) SHT P0.1 WATER HEATER DETAIL, THERMAL
 EXPANSION CONTROL IS REQUIRED 607.3.2. -
 DIELECTRIC UNIONS NOT APPROVED FOR WATER
 USE, DELETE FROM DETAIL. (SEE PLUMBING
 NOTE #14).
 8) SHT P0.1 WATER HEATER DETAIL, PROVIDE
 INFORMATION FROM ENGINEER TO SHOW THAT
 POINT LOADING OF WATER HEATER ON BOTTOM
 CORD OF JOISTS HAS BEEN ADDRESSED. SEC
 1603.3. (APPROX. 300 LBS.).
 9) SHT P2.1 STATES "CONNECT TO EXISTING
 WATER & SEWER" PLEASE CLAIRFY.
 10) SHT P4.1 CENTER ROOF, - ROOF DRAIN
 CALLS OUT 8,000 SF, BUT OVERFLOW DRAIN
 ONLY INDICATES 2500 SF. PLEASE CLAIRFY.
 SECTION 104.2.1
 11) SUBMIT A STORM RISER DIAGRAM. SHOW
 ALL PIPE SIZING AND INDICATE TERMINATION
 OF PIPE. 104.3.1.1
 12) SHT P4.1 ROOF PIPING SUPPORT DETAIL
 FOR CONDENSATE, IS THE CONCRETE STEPPING
 STONES ON THE ROOF AN ENGINEERED SYSTEM
 THAT WILL WITHSTAND 140 MPH WIND SPEED?
 INDICATE HOW STONES WILL BE ATTACHED TO
 THE ROOF. INDICATE HOW SLOPE WILL BE
 MAINTAINED FROM ROOF UNITS TO ROOF DRAIN
 13) SHT P4.1 ROOF PIPING SUPPORT DETAIL
 FOR CONDENSATE, DETAIL INDICATES STONES
 TO BE 6'0" ON CENTER, TABLE 308.5 STATES
 4'0" MAX FOR PVC PIPE HORIZONTAL SPACING
 PLEASE CLAIRFY.
 14) PVC EXPOSED TO UV LIGHT RAYS FROM
 THE SUN SHALL BE PAINTED WITH AN APPROV-
 ED PAINT. (NON OIL BASE)
 15) SHT P5.1 DOMESTIC WATER ISOMETRIC,
 WATER HAMMER ARRESTORS SHALL BE LOCATED
 NEAR THE FIXTURE IN AN "EFFECTIVE RANGE"
 NOT IN THE CEILING AS SHOWN. PDI-WH 201
 AND MANUF. INSTALLATION INSTRUCTIONS.
 (SEE PLUMBING NOTE #13 SHT P0.1)
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]