2004-02-25 00:00:00DENIED:
 1.PLEASE CLARIFY NOTE ON PLANS SHEET
 M2.1, ALL OPEN DUCTS TO BE COVERED WITH
 STAINLESS WIRE MESH.WILL THIS BE A
 FINISHED PRODUCT OR FOR FUTURE?EXPLAIN
 RATIONAL FOR NOT INSTALLING A GRILLE.
  
 2.FAN SHUTDOWN BY DUCT SMOKE DETECTORS
 SHALL HAVE NOTIFICATION TO ALARM/STROBE
 IN NORMALLY OCCUPIED AREAS.
  