Plan Review Notes
Plan Review Notes For Permit 04020363
Permit Number 04020363
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-02-13 00:00:001) SEPARATE PLANS AND PERMITS REQUIRED
 FOR THE FIRE ALARM SYSTEM. FIRE
 ALARM SYSTEM SHALL BE UL LISTED FOR
 CENTRAL STATION SERVICE. A CERTIFICATE
 FOR CENTRAL STATION SERVICE SHALL
 BE PROVIDED AT TIME OF FIRE ALARM
 PERMIT APPLICATION.
  
 2) NOTES ON PAGE FAO.1. ARE INCORRECT.
 NOTES 17 AND 18 ARE TO BE REVISED.
  
 3) A KNOX-BOX WILL BE REQUIRED.
  
 4) NO EXIT SIGN PRESENT DIRECTLY IN
 FRONT OF LOUNGE DOOR TO DIRECTING
 PERSON TO THE LOUNGE EXTERIOR EXIT.
  
 5) BUILDING ADDRESS NOT SHOWN ON
 ELEVATION DRAWING. BUILDING ADDRESS
 SHALL BE A MINIMUM OF 6" HIGH.
  
 6) TENANT SPACE B IS TO BE FIRE
 SPRINKLER PROTECTED WHEN SPACE A IS.
  
 7) NO FIRE SPRINKLER PLANS PROVIDED.
  
 8) PLEASE INDICATE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 9) PLEASE PROVIDE A LIFE SAFETY
 PLAN FOR REVIEW.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910