2004-02-20 00:00:00 | ***************** UNSAT ************** |
| |
| 1)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125%. 215.3,230.42 ETC. |
| |
| 2)NOTE: PLEASE SHOW LOCATION OF MAIN |
| ON THE OUTSIDE OF BLDG, ON E3.1 |
| |
| 3)NOTE: PLANS SHOWS ACCESS INTO ELECTR- |
| -CAL THROUGH JAN. CLOSET. PLEASE SEE |
| THIS WILL NOT BE PERMITTED. MET WITH |
| FIRE MARSHAL MIKE CARSILLO AND NOTES |
| ON ELECTRICAL NOTES. LS 101, NEC 110.26 |
| ETC. |
| |
| 4)NOTE: PLEASE LABEL EACH OF THE 400A |
| DISC'S IN 1200A MLO. |
| |
| 5)NOTE: PLEASE SEE THAT SERVICE DISC |
| MEANS FOR TENANT "B" IS LOCATED INSIDE |
| PRIMARY TENANT SPACE. PLEASE VERIFY |
| IF THIS TENANT'B' WILL PART OF THE SAME |
| OFFICE.? |
| TENANT "B" MUST HAVE ACCESS TO THEIR |
| DISC MEANS W/OUT GOING INTO ANOTHERS |
| SPACE. |
| A COMMON ELECTRICAL RM MAY BE AN ANSWER? |
| AS SHOWN, IF ONE OFFICE IS CLOSED, OTHER |
| TENANT WILL NOT HAVE ACCESS.? |
| |
| PLEASE SEE FIRE REVIEW COMMENTS AS WILL |
| HAVE AN AFFECT ON ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |