Plan Review Notes For Permit 04020227 |
Permit Number |
04020227 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-05-28 00:00:00 | 1) THE FIRE DEPARTMENT CONNECTION SHALL | | BE WITHIN 150 FEET OF A FIRE HYDRANT. | | | | 2) THE FIRE DEPARTMENT CONNECTION SHALL | | BE PROVIDED WITH SEVEN AND HALF FEET | | OF CLEARANCE. | | | | 3) THE FIRE DEPARTMENT CONNECTION SHALL | | NOT BE PLACED IN AN AREA SUBJECT TO | | VEHICLE DAMAGE. | | | | 4) SPRINKLER HEADS USED IN THE DRIVE | | THRU CANOPY SHALL BE CORROSION RESISTANT | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | 835-2910 |
|