Plan Review Notes
Plan Review Notes For Permit 04020227
Permit Number 04020227
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2004-05-28 00:00:001) THE FIRE DEPARTMENT CONNECTION SHALL
 BE WITHIN 150 FEET OF A FIRE HYDRANT.
  
 2) THE FIRE DEPARTMENT CONNECTION SHALL
 BE PROVIDED WITH SEVEN AND HALF FEET
 OF CLEARANCE.
  
 3) THE FIRE DEPARTMENT CONNECTION SHALL
 NOT BE PLACED IN AN AREA SUBJECT TO
 VEHICLE DAMAGE.
  
 4) SPRINKLER HEADS USED IN THE DRIVE
 THRU CANOPY SHALL BE CORROSION RESISTANT
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910