Plan Review Notes
Plan Review Notes For Permit 04020209
Permit Number 04020209
Review Stop M
Sequence Number 1
Notes
Date Text
2004-02-21 00:00:00PROVISO
 ----------------------------------------
 R/A JUMPERS SHOWN IN BEDROOMS 2 AND 3
 ARE INSUFFICIENT PER THE REQUIREMENTS OF
 FBC(M) 601.4.
 9" ROUND FLEX JUMPERS WOULD BE SUF-
 FICIENT FOR THE 7" ROUND DROPS SHOWN IN
 THESE ROOMS.
  
 PLEASE CALL IF YOU HAVE ANY QUESTIONS
 RONALD J REGUEIRO 561-805-6734