2004-03-15 00:00:00 | BUILDING PLAN REVIEW |
| *******DENIED******* |
| ROBERT BROWN(561) 805 6716 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| |
| 1) 61G1-16.004FL. ADMIN. CODE.PLANS |
| PREPARED BY A REGISTERED ARCHITECT SHALL |
| INCLUDE THE PRINTED NAME AND LICENSE |
| NUMBER OF THE ARCHITECT SEALING THE |
| PLANS.ALSO, THE RAISED SEAL DOES NOT |
| SHOW THE LICENSE NUMBER OF STUART |
| BRENNER (AR0014503).PROVIDE THE |
| REQUIRED INFORMATION ON EACH |
| ARCHITECTURAL SHEET. |
| |
| 2) BREAKFAST AREA HORIZONTAL SLIDING |
| WINDOW PRODUCT APPROVALS.THESE TWO |
| WINDOWS ARE 6060 HR AND THEREFOR EXCEED |
| THE MAXIMUM HEIGHT STATED ON DRAWING |
| SHEET 3 OF THE SUBMITTED PRODUCT |
| APPROVAL NOA# 01-0724.05.AMEND THE |
| SIZE/TYPE OF THE WINDOWS OR SUBMIT A |
| PRODUCT APPROVAL WHICH IS APPLICABLE. |
| |
| 3) FBC 1015.3SHEET A-8, DETAIL 13, |
| STAIR GUARDRAIL.THE INTERMEDIATE RAILS |
| SHALL BE SPACED SO AS TO RESIST THE |
| PASSAGE OF A 4" SPHERE.AMEND/ANNOTATE |
| THE PLANS. |
| |
| --PROVISO-- |
| FBC 1606.1.4HURRICANE MISSILE IMPACT |
| PROTECTION SHALL BE PROVIDED UNDER A |
| SEPARATE PERMIT APPLICATION. |
| |
| **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| |
| END OF REVIEW COMMENTS |