Plan Review Notes
Plan Review Notes For Permit 04020114
Permit Number 04020114
Review Stop E
Sequence Number 3
Notes
Date Text
2004-08-19 00:00:00****** NOTES REDLINED *****
  
 SIGN CIRCUIT STILL SHOWN ON WITH SAME
 CIRCUIT AS SHOW WINDOWS. THIS MUST BE
 ON SEPARATE CIRCUITS. 210.62,220.12,
 600.5
  
 PLEASE SEE VALUE FOR COMPLETE SCOPE OF
 WORK IS TO BE ADJUSTED BY BLDG PLAN
 REVIEW.
 ***************************************
 AN ELECTRICAL PERMIT WILL BE REQUIRED
 FOR NEW WORK AND TO CORRECT ELECTRICAL
 WORK UNDER PREVIOUS PERMIT NOT TO CODE.
 ***************************************