Notes |
Date |
Text |
2004-07-10 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 BUILDING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) DUE TO CHANGE OF OCCUPANCY THE TOILET | | ROOM SHALL HAVE TO COMPLY WITH 11-4.22, | | 11-4.16, & 11-4.19 AND ALL SUBSECTIONS. | | 2) PER COMMENT RESPONSE FOR A GREASE IN- | | TERCEPTOR, A SAMPLE POINT SHALL BE RE- | | QUIRED ON SANITARY LINE FROM DELI AREA | | AND UPSTREAM OF THE TOILET ROOM. PLEASE | | SHOW ON PLANS AND ON SANT. RISER DIAGRAM | | SECTION 104.2.1 | | 3) PER TABLE A DRINKING FOUNTAIN IS RE- | | QUIRED. ALSO SEE SECTION 410.1 | | 4) UNABLE TO READ INFORMATION REQUIRED | | ON SEAL OF PLANS. INFORMATION REQUIRED | | PER FAC 61G1-16.001/002 & FS 481.2055. | | A NEW SEAL MAY BE REQUIRED. | | 5) INFORMATION MISSING ON THE TITLE | | BLOCK REQUIRED BY FAC 61G1-16.004 | | (6) A SPACE FOR PRINTED NAME OF THE PER- | | SON SEALING THE DOCUMENT. | | 6) THE ORIGINAL APPLICATION IS REQUIRED | | FOR PERMIT. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|