Plan Review Notes
Plan Review Notes For Permit 04020114
Permit Number 04020114
Review Stop P
Sequence Number 2
Notes
Date Text
2004-07-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) DUE TO CHANGE OF OCCUPANCY THE TOILET
 ROOM SHALL HAVE TO COMPLY WITH 11-4.22,
 11-4.16, & 11-4.19 AND ALL SUBSECTIONS.
 2) PER COMMENT RESPONSE FOR A GREASE IN-
 TERCEPTOR, A SAMPLE POINT SHALL BE RE-
 QUIRED ON SANITARY LINE FROM DELI AREA
 AND UPSTREAM OF THE TOILET ROOM. PLEASE
 SHOW ON PLANS AND ON SANT. RISER DIAGRAM
 SECTION 104.2.1
 3) PER TABLE A DRINKING FOUNTAIN IS RE-
 QUIRED. ALSO SEE SECTION 410.1
 4) UNABLE TO READ INFORMATION REQUIRED
 ON SEAL OF PLANS. INFORMATION REQUIRED
 PER FAC 61G1-16.001/002 & FS 481.2055.
 A NEW SEAL MAY BE REQUIRED.
 5) INFORMATION MISSING ON THE TITLE
 BLOCK REQUIRED BY FAC 61G1-16.004
 (6) A SPACE FOR PRINTED NAME OF THE PER-
 SON SEALING THE DOCUMENT.
 6) THE ORIGINAL APPLICATION IS REQUIRED
 FOR PERMIT.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]