2004-08-13 00:00:00*** UNSAT ***
  
 PLEASE SEE THE FOLLOWING COMMENTS.
 PLANS ARE COMING BACK FOR PLUMB COMMENTS
  
 1)NOTE: PLEASE SEE REQUIRED SIGN CIRCUIT
 PER 600.5 IS SHOWN ON SAME CIRCUIT WITH
 SHOW WINDOWS. THESE ARE EACH REQUIRED TO
 BE ON SEPARATE CIRCUITS.
  
 2)NOTE: PLEASE SEE PLANS INDICATE A NEW
 WATER HEATER AND CIRCUIT YET PANEL
 SCHEDULE INDICATES EXISTING WH?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE SEE NEW RECEPT #29 TO
 ALSO BE GFI. 210.8
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  