Plan Review Notes
Plan Review Notes For Permit 04020114
Permit Number 04020114
Review Stop P
Sequence Number 1
Notes
Date Text
2004-02-13 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 BUILDING
  
 1) SANT. RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS. 909.1 ONLY THE FIX-
 TURES WITHIN THE BATHROOM GROUP SHALL
 CONNECT TO THE WET-VENTED HORIZONTAL
 BRANCH DRAIN. ANY ADDITIONAL FIXTURES
 SHALL DISCHARGE DOWNSTREAM OF THE WET
 VENT. THE MOP BASIN AND HAND SINK SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM FIX-
 TURES.
 2) SECTION 3401.2.2.1 IF THE OCCUPANCY
 CLASSIFICATION OR OCCUPANCY SUBCLASSI-
 FICATIONS OF ANY EXISTING BUILDING OR
 STRUCTURE IS CHANGED, THE BUILDING,
 ELECTRICAL, GAS, MECHANICAL AND PLUMBING
 SYSTEMS SHALL BE MADE TO CONFORM TO THE
 INTENT OF THE TECHNICAL CODES AS REQUIR-
 ED BY THE BUILDING OFFICIAL.
 3) INDICATE TYPE OF OCCUPANCY THIS WILL
 BE.
 4) IF OCCUPANCY IS A FOOD SERVICE TYPE,
 AS INDICATED BY FIXTURES BEING ADDED, IT
 WILL BE REQUIRED TO CONTACT RODNEY COMPO
 ENVIRONMENTAL COMPLIANCE WASTE ORD #2938
 -96. (561) 837-4074 - THIS IS TO DETER-
 MINE IF A GREASE INTECEPTOR IS REQUIRED.
 5) THE TYPE OF OCCUPANCY SHALL DETERMINE
 IF THE DBPR HOTEL AND RESTURANT DIVISION
 OR PALM BEACH COUNTY HEALTH UNIT WILL BE
 REQUIRED TO REVIEW THE PLANS.
 6) MORE INFORMATION REQUIRED. SUBMIT A
 FLOOR PLAN FOR THE BUILDING INDICATING
 ALL ROOMS, TOILET ROOMS, DRINKING
 FOUNTAINS ECT. SECTION 104.2.1.2
 7) OTHER COMMENTS MAY BE FORTHCOMMING
 ACCORDING TO RESPONSE TO THESE COMMENTS.
 8) ALL DRAWINGS SHALL BEAR THE NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. 104.2.1
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved