2004-07-14 00:00:00 | *************** UNSAT ************** |
| |
| PLEASE SEE THAT PLANS SUBMITTED |
| FOR ELECTRICAL REVIEW ARE NOT THE SAME |
| AS SUBMITTED UNDER A SEPARATE ELECTRICAL |
| PERMIT. # 04050876 |
| PLEASE SEE THAT DUE TO CHANGE IN OCCU- |
| -PANCY ALL ELETCRICAL WORK AND PLANS |
| MUST BE BROUGHT UP TO CODE FOR COMM |
| MERCHANTILE OCCUPIED BLDG. |
| PLANS SUBMITTED UNDER SEPARATE PERMIT |
| DID NOT MEET COMPLETE CODE COMPLIANCE |
| FOR ITS INTENT AND USE. |
| |
| 1)NOTE: PLEASE SEE 600.5 FOR MISSING |
| REQUIRED SIGN CIRCUIT. |
| |
| 2)NOTE: PLEASE SEE 210.62 FOR MIN REQ- |
| -UIRED SHOW WINDOW RECEPTS. |
| |
| 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| -ING OF EM/EXT LTS. |
| |
| 4)NOTE: PLEASE SEE SEC'S/ FEEDERS ARE |
| NOT LARGE ENOUGH FOR SERVICE SIZE SHOWN. |
| PLEASE SEE 310.16. |
| |
| 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.3,230.42 |
| |
| 6)NOTE: PLEASE SEE THAT RAISED SEAL FOR |
| ARCHITECT MUST BE CLEAR AND VISABLE WITH |
| ALL INFORMATION ON SAID SEAL. |
| FS 481.221 |
| |
| 7)NOTE: PLEASE SEE 210.8B3 FOR MIN |
| GFI RECEPTS TO MEET CODE COMPLIANCE FOR |
| KITCHEN AREA. |
| |
| 8)NOTE: PLEASE SEE 3-PHASE BREAKERS |
| SHOWN ON PANEL SCHEDULE YET, SERVICE IS |
| SHOWN AS 1-PHASE? ALONG W/ LOAD DETAIL? |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CITY OF WEST PALM BEACH |
| CONSTUCTION SERVICES DEPT. |
| 561-805-6717 |