2004-06-29 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| 1.)SEPARATE PERMITS REQUIRED. |
| |
| 2.)HISTORIC APPROVAL REQUIRED.PLEASE |
| HAVE THE PLANS STAMPED BY HISTORIC. |
| |
| 3.)SEE THE PREVIOUS LISTS.HOW WILL |
| THE HANDRAIL BE FASTENED TO COMPLY |
| WITH FBC1608.2?IN OTHER WORDS, HOW |
| WILL YOU ATTACH THIS TO THE WALL?THIS |
| CORRECTION HAS BEEN ON EACH LIST; PLEASE |
| HAVE THE ENGINEER CALL ME IF HE DOESN'T |
| UNDERSTAND THE CORRECTION. |
| |
| 4.)CONNECTOR MTS37 ISN'T IN THE |
| CATALOG.YOU GAVE A SPEC SHEET FOR |
| MST37.FASTENING STILL CONFLICTS. |
| PLEASE SEE ATTACHED.FASTENING FOR SP5 |
| ALSO CONFLICTS (SEE ATTACHED).CHECK |
| ALL CONNECTORS.PLEASE HAVE THE |
| ENGINEER CONTACT ME IF HE DOES NOT |
| UNDERSTAND THIS CORRECTION AS IT HAS |
| BEEN MADE 3 TIMES WITHOUT BEING PROPERLY |
| CORRECTED. |
| |
| 5.)ALL OF THE OTHER PLANS SUBMITTED |
| REFERRED TO FBC2001.NOW THE PLANS |
| HAVE BEEN CHANGED TO FBC2002.THE |
| GOVERNING CODE IS STILL FBC2001, PLEASE |
| CORRECT. |
| |
| 6.)A 4X FEE HAS BEEN CHARGED PER |
| FS553.80(2)(B). |