Plan Review Notes For Permit 04020057
Permit Number 04020057
Review Stop P
Sequence Number 3
Notes
Date Text
2004-05-25 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) SHT A4 SANITARY RISER DIAGRAM IS UN-
 CLEAR AND DOES NOT MEET CODE. SECTION
 104.2.1. - REMOVE ALL INFORMATION FROM
 THE SANITARY RISER DIAGRAM THAT HAS NO
 RELEVANCE TO THE RISER. THE FLOOR JOISTS
 MAKE THE RISER DIAGRAM IMPOSSIBLE TO
 REVIEW.
 - THE WASH MACHINE SHALL CONNECT TO THE
 STACK DOWNSTREAM OF THE KITCHEN SINK.
 - THE WASH MACHINE REQUIRES A STANDPIPE
 - THE TUB REQUIRES A TRAP
 - SEE RED LINE CORRECTIONS FOR DIAGRAM
 SECTIONS: 1002.1 - 802.4
  
 2) THE PERSONAL SIGNATURE OF THE ARCHIT-
 ECT SHALL APPEAR ON ALL ARCHITECTURAL
 DOCUMENTS TO BE FILED FOR PUBLIC RECORD.
 INITIALS ARE NOT ACCEPTABLE. FAC 61G1-16
 .003 & FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]