2004-05-14 00:00:00*********** UNSAT ***********
  
 1)NOTE: PLEASE SEE PLANS STILL HAVE
 PLACES WHERE 1999 NEC IS REFERENCED?
  
 2)NOTE: PLEASE SEE FAC 61G15-23.002
 PLEASE INCLUDE ALL INFORMATION ON TITLE
 BLOCK FOR ENGINEER. THIS IS REQ'D TO BE
 PRINTED ON PLANS. PLEASE ALSO SEE FS
 471.025, A SIGNATURE IS REQ'D, PER
 FS AND FBPE'S INITIALS ARE NOT PERMITTED
 PLEASE NOTE: THIS IS TO PROTECT THE
 ENGINEER/ FIRMS.
 SIGNATURE INFORMATION HAS BEEN GONE OVER
 W/ MR BUCK AND HE IS NOW AWARE OF WHAT
 NEEDS TO BE DONE FOR THIS.
  
 3)NOTE: PLEASE SEE RISER, AN EQUIPMENT
 GROUND NOTE SHOWS AN EQUIP GRND FROM
 TO METER, AND FROM METER TO MAIN ALSO.
 PLEASE SEE 250.6,250.24, AN EQUIP GRND
 IS ONLY INSTALLED "AFTER THE FIRST MEANS
 OF DISC". PLEASE ADJUST RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  