2004-04-15 00:00:00********** UNSAT ***************
  
 1)NOTE: PLEASE SEE PLANS REFERENCE
 DIFFERENT NEC CODES. 2002, 2001 AND 1999
 WE ARE UNDER THE 2002 NEC AND ALL REF'S
 SHOULD BE TO THE 2002.
  
 2)NOTE: PLEASE SEE NOW AN EQUIPMENT
 GROUNDING CONDUCTOR IS NOW BEING SHOWN
 FROM METER TO THE FIRST MEANS OF DISC
 ALSO. PLEASE NOTE, THE EQUIPMENT GRND
 IS ONLY INSTALLED AFTER THE FIRST MEANS
 OF DISC. PER 250.24
  
 3)NOTE: PLEASE SEE 220.18 FOR A MIN OF
 5KW FOR DRYER TO BE FIGURED.
 PLEASE SEE PANEL SCHEDULE SHOWS 4.5KW,
 PLEASE ALSO SEE LOAD CALCULATIONS DO NOT
 INCLUDE DRYER.
 PLEASE SEE MICROWAVE THAT IS SHOWN ON
 LOAD CALCS IS NOT ON PANEL SCHEDULE.
  
 PLEASE VERIFY THE # OF ARC FAULT CIRCUIT
 -S SHOWN ON PANEL SCHEDULE.
  
 4)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT AND REAR RECEPTS OF DWELLING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW