Plan Review Notes
Plan Review Notes For Permit 04020057
Permit Number 04020057
Review Stop B
Sequence Number 2
Notes
Date Text
2004-04-20 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST, COMMENTS
 2,6,7, SECOND PART OF 8, 9,10, 12, AND
 15.A COPY HAS BEEN PROVIDED.
  
 2.)SEE PREVIOUS LIST, #10.THE
 FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVAL IS REQUIRED
 FOR THE WINDOWS, DOORS AND SHUTTERS
 IN ADDITION TO THE TEST REPORTS
 PROVIDED.PROVIDE A LIST OF ALL
 CONNECTORS WITH THE FLORIDA PRODUCT
 APPROVAL.FAC9B-72,
 WWW.FLORIDABUILDING.ORG
  
 3.)PROVIDE THE DISTANCE BETWEEN THE
 TWO BUILDINGS.SHOW COMPLIANCE WITH
 FBC TABLE 600.PROVIDE AN ELEVATION OF
 THE EAST SIDE OF THE PORTION OF THE
 BUILDING (MAIN RESIDENCE) THAT FACES
 THE 2 STORY ACCESSORY BUILDING.
  
 4.)COMMENT #15 WAS APPARENTLY
 ADDRESSED BY SHOWING PRESSURES OF
 +50/-53 ON THE PLAN (A1), BUT THE NOTES
 STILL INDICATE 57 (TWO STORY).
  
 5.)NAILING FOR SIMPSON MTS30
 CONFLICTS WITH THE CATALOG; REVISE.
 CHECK ALL CONNECTORS.
  
 6.)SEPARATE PERMITS REQUIRED.
  
 7.)SEE ATTACHED FS553.80(2)(B).