Plan Review Notes For Permit 04020057 |
Permit Number |
04020057 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-13 00:00:00 | DENIED; | | 1.AUTOMATIC CLOTHES WASHER REQUIRED. SEE | | FBC PLUMBING TABLE 403.2 ONE AND TWO | | FAMILY DWELLINGS. | | 2.SANITARY RISER DIAGRAM NOT TO CODE. | | KITCHEN SINK IS NOT VENTED, BATHROOM | | CANNOT BE INSTALLED AS DRAWN. | | 3.IS W/H 30 OR 50 GAL.? | | 4.H2O RISER DIAGRAM, SHOCK ARRESTORS NOT | | AIR CHAMBERSARE REQUIRED PER SEC 604.9 | | 5.PLUMBING NOTE #1. BUILDING SEWER IS | | REQUIRED TO BE INSTALLED TO THE PUBLIC | | SEWER SYSTEM. SEPIC TANK NEEDS TO BE | | REMOVED. | | 6.NOTE # 10 REMOVE NOTE HOT WATER SHOULD | | 120 DEG. ONLY COMMERCIAL DISHWASHER | | REQUIRE 180 DEG. WATER. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|