Plan Review Notes
Plan Review Notes For Permit 04020057
Permit Number 04020057
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-11 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEPARATE PERMITS REQUIRED.
  
 2.)HISTORIC APPROVAL REQUIRED.
  
 3.)IMPROVEMENTS OVER 50% MUST COMPLY
 WITH FBC3401.7.2.6; NOTE ON PLAN.
  
 4.)PROVIDE A SURVEY FOR THIS PROPERTY.
  
 5.)THE ENGINEER'S LICENS NUMBER IS TO
 BE PRINTED ON EACH SHEET, FAC61G15-23.00
 2.
  
 6.)THE STAIR DETAIL 3-A1 DOES NOT
 COMPLY WITH FBC1007.3.1(1).DO THESE
 DIMENSIONS INDICATE EXISTING
 CONDITIONS?SEE FBC1001.3.
  
 7.)A1, SCOPE OF BUILDING WORK
 INDICATES AN UPSTAIRS KITCHEN.IS THIS
 CORRECT?NONE IS SHOWN ON THE FLOOR
 PLAN.
  
 8.)3-A1, HANDRAIL IS TO COMPLY WITH
 FBC1007.5 (34-38" ABOVE TREAD).ALSO
 MUST COMPLY WITH FBC1608.2.HOW WILL
 THE RAIL BE FASTENED TO COMPLY WITH
 FBC1608.2?
  
 9.)3-A1 SHOWS A STRAP SECURED TO
 A SLAB, CONFLICTS WITH THE OTHER DETAILS
 WHICH SHOW WOOD.
  
 10.) FLORIDA STATEWIDE, LOCAL OR SITE
 SPECIFIC PRODUCT APPROVALS REQUIRED.
 WWW.FLORIDABUILDING.ORG.PROVIDE A LIST
 OF ALL CONNECTORS WITH FLORIDA PRODUCT
 APPROVAL NUMBERS.
  
 11.)CORNER FRAMING DETAIL, APPLICATION
 CONFLICTS WITH USP CATALOG FOR RS100.
 ADDRESS.
  
 12.)PROVIDE DESIGN UPLIFT INFORMATION.
  
 13.)SPECIFY ALL CONNECTORS,
 CONTINUOUS FROM THE FOUNDATION THROUGH
 THE ROOF, ON ALL DETAILS.
  
 15.)THE DOOR PRODUCT APPROVAL HAS A
 LIMITATION OF +50/-53.IT APPEARS THAT
 THE DESIGN PRESSURE FOR THIS OPENING
 IS -57.