Plan Review Notes
Plan Review Notes For Permit 04011436
Permit Number 04011436
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-02-02 00:00:00*********DENIED*************************
 WATER SUPPLY SAFETY MARGIN IS 3.558 PSI
 PER CITY OF WEST PALM BEACH FIRE MARSHAL
 (AHJ) MINIMUM SAFETY MARGIN REQUIRED IS
 5.0 PSI.
  
 NATE MCCRAY, CAPTAIN
 805-6722 OR 835-2910