2004-02-11 00:00:00 | PROVISO: | | 2ND FLOOR - EXISTING BEDROOM WITH 200 | | CFM OF SUPPLY AIR WILL REQUIRE A LARGER | | TRANSFER.PER 2001 FBC(M) 601.4 | | EXCEPTION #2, TRANSFER GRILLES SHALL | | USE 50 SQUARE INCHES PER 100 CFM OF | | SUPPLY AIR.PLAN INDICATES A 12" X 6" | | WHICH EQUALS ONLY 72 SQUARE INCHES. | | PLEASE REVISE PLANS TO COMPLY. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|