2004-02-11 00:00:00PROVISO:
 2ND FLOOR - EXISTING BEDROOM WITH 200
 CFM OF SUPPLY AIR WILL REQUIRE A LARGER
 TRANSFER.PER 2001 FBC(M) 601.4
 EXCEPTION #2, TRANSFER GRILLES SHALL
 USE 50 SQUARE INCHES PER 100 CFM OF
 SUPPLY AIR.PLAN INDICATES A 12" X 6"
 WHICH EQUALS ONLY 72 SQUARE INCHES.
 PLEASE REVISE PLANS TO COMPLY.
  