Plan Review Notes For Permit 04011355 |
Permit Number |
04011355 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-09 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} NOTE THAT THE SIGNATURE OF THE EN- | | GINEER IS REQUIRED ON HIS/HER SEAL PER | | 61G15-23.002 FLORIDA ADMINISTRATIVE | | CODE. INITIALS ARE NOT ACCEPTABLE PER | | F.B.P.E. | | | | 2} THE INSTA HOT SHOWN ON THE PLAN IS | | NOT SHOWN IN THE LOAD CALCULATION/PANEL | | SCHEDULE. PLEASE INCLUDE SAME. | | | | 3} PLEASE SEE 220.3(B)(4) FOR RECESSED | | LUMINAIRE CALCULATION. | | | | 4} SEE 220.18 FOR DRYER CALCULATION | | REQUIREMENTS. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|