2004-02-09 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} NOTE THAT THE SIGNATURE OF THE EN-
 GINEER IS REQUIRED ON HIS/HER SEAL PER
 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE. INITIALS ARE NOT ACCEPTABLE PER
 F.B.P.E.
  
 2} THE INSTA HOT SHOWN ON THE PLAN IS
 NOT SHOWN IN THE LOAD CALCULATION/PANEL
 SCHEDULE. PLEASE INCLUDE SAME.
  
 3} PLEASE SEE 220.3(B)(4) FOR RECESSED
 LUMINAIRE CALCULATION.
  
 4} SEE 220.18 FOR DRYER CALCULATION
 REQUIREMENTS.
  