Plan Review Notes
Plan Review Notes For Permit 04011145
Permit Number 04011145
Review Stop P
Sequence Number 2
Notes
Date Text
2004-03-23 00:00:00REVISION DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1) A SANITARY AND A WATER RISER DIAGRAM,
 (ISOMETRIC), ARE REQUIRED PER SECTION
 104.3.1.1.
 2) SHT P8.2 DETAIL #13 SHOW GRAB BARS
 SECTION 11-4.16.4, TOILET HEIGHT SECTION
 11-4.16.3, LAV HEIGHT AND CLEARANCES
 SECTION 11-4.19.2, EXPOSED PIPES AND
 SURFACES 11-4.19.4 ON DETAIL.
 3) PER FAC 61G1-16.004(6) A SPACE FOR
 THE PRINTED NAME OF THE PERSON SEALING
 THE DRAWINGS IS REQUIRED.
 4) PER FS 481.219(2) A CERTIFICATE OF
 AUTHORIZATION SHALL BE REQUIRED FOR A
 CORPORATION, PARTNERSHIP, OR PERSON
 PRACTICING UNDER A FICTITIOUS NAME,
 OFFERING ARCHITECTURAL SERVICES TO THE
 PUBLIC JOINTLY OR SEPARATELY.
  