Plan Review Notes For Permit 04011145 |
Permit Number |
04011145 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-03-23 00:00:00 | REVISION DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | FBC-2001 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1) A SANITARY AND A WATER RISER DIAGRAM, | | (ISOMETRIC), ARE REQUIRED PER SECTION | | 104.3.1.1. | | 2) SHT P8.2 DETAIL #13 SHOW GRAB BARS | | SECTION 11-4.16.4, TOILET HEIGHT SECTION | | 11-4.16.3, LAV HEIGHT AND CLEARANCES | | SECTION 11-4.19.2, EXPOSED PIPES AND | | SURFACES 11-4.19.4 ON DETAIL. | | 3) PER FAC 61G1-16.004(6) A SPACE FOR | | THE PRINTED NAME OF THE PERSON SEALING | | THE DRAWINGS IS REQUIRED. | | 4) PER FS 481.219(2) A CERTIFICATE OF | | AUTHORIZATION SHALL BE REQUIRED FOR A | | CORPORATION, PARTNERSHIP, OR PERSON | | PRACTICING UNDER A FICTITIOUS NAME, | | OFFERING ARCHITECTURAL SERVICES TO THE | | PUBLIC JOINTLY OR SEPARATELY. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|