2004-03-02 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04011145
 ADD: 5500 N VILLAGE BLVD# 102 & 103
 CONT: BUTLER CONSTRUCTION
 TEL: (561)644-9397
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET 3.1 SUITE 102 DOOR 102-21 EXIST
 ING EXIT DOOR & EXIT DOOR FROM STAIRWELL
 OPPOSE EACH OTHER, NOT A CLEAR AND
 UNOBSTRUCTED EXIT 1001.1.3. / TABLE
 1004 CLEAR MINIMUM FOR EXIT DOORS IS
 32". SEE 1003.2.3.1.
  
 2) THIS SAME CONFIGURATION OCCURS ON
 SHEET 3.2 OPPOSITE END OF THE BUILDING
 IN SUITE 103.
  
 3) SHEET 10.1 NOTE ON KEY PAD LOCK CON-
 TROL. PROVIDE ADDITIONAL INFORMATION
 IF ELEC FAILS ?
  
 4)704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
 2)NOTE: PLEASE SEE BLDG PLAN REVIEW
 NOTES. PLEASE CORRELATE PLANS/PAPERWORK
 FOR COTTAGES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]