Plan Review Notes For Permit 04010955 |
Permit Number |
04010955 |
|
Review Stop |
M |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2004-05-12 00:00:00 | DENIED: | | REVISION INDICATES CHANGE IN THE RETURN | | AIR JUMPER FROM THE MASTER SUITE.THE | | DUCT SIZE HAS NOT CHANGED.THE PROPER | | SIZE PER THE REVISED 2001 FBC(M) 601.4 | | EXCEPTION #1 & 3, THE MINIMUM SIZE FOR | | THE JUMPER SHALL BE 16" NOT 14" AS | | INDICATED. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|