2004-05-12 00:00:00DENIED:
 REVISION INDICATES CHANGE IN THE RETURN
 AIR JUMPER FROM THE MASTER SUITE.THE
 DUCT SIZE HAS NOT CHANGED.THE PROPER
 SIZE PER THE REVISED 2001 FBC(M) 601.4
 EXCEPTION #1 & 3, THE MINIMUM SIZE FOR
 THE JUMPER SHALL BE 16" NOT 14" AS
 INDICATED.
  