2004-03-16 00:00:00 | BUILDING REVIEW PROVISO: |
| 1-PROVIDE COMPLETE INFORMATION FOR STORM |
| SHUTTERS UNDER A SEPARATE PERMIT. |
| 2-PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: A)SINGLE HUNG WINDOWS: |
| NEED DADE COUNTY DRAWINGS THAT MATCH |
| FLORIDA PRODUCT APPROVAL. |
| B)FIXED WINDOWS: NEED DADE COUNTY DWGS |
| THAT MATCH FLORIDA PRODUCT APPROVAL. |
| **NEED ARCHED & RECTANGULAR WINDOWS. |
| C)CLARIFY WHICH PRODUCT APPROVAL IS FOR |
| GARAGE SIDE DOOR AND WHICH ONE IS FOR |
| ENTRY DOORS. |
| D)PROVIDE "BENCHMARK" OR "THERMA-TRU" |
| DWGS THAT MATCH FLORIDA PRODUCT APPRO- |
| VAL ACCORDINGLY. |
| E)NEED TO CLARIFY WHICH OPENING IS GOING |
| TO BE USED FOR MEANS OF ESCAPE WHEN |
| SHUTTERS ARE INSTALLED. SEC. 1005.4.5 |
| FBC 2001. |
| F)GARAGE DOOR PRODUCT APPROVAL IS FOR |
| 110MPH WIND LOAD ZONE. WHERE ARE IN |
| 140MPH ZONE. RESUBMIT AS REQUIRED. |
| **NOTE: THERE ARE SOME |
| G)ROOF TILE FOR 140MPH WIND LOAD. |
| H)ALL STRUCTURAL CONNECTORS. |
| |
| 3-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| INSTALLATION OF SLIDING GLASS DOORS & |
| TRANSOM ABOVE ASSEMBLY ATTACHED TO THE |
| HORIZONTAL STRUCTURAL STEEL HEADER. |
| SPECIFY ALL FASTENERS. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 4-NEED 7/8 MIN. STUCCO THICKNESS AT ALL |
| FRAMED AREAS AS REQUIRED BY ASTM C926. |
| REVISE ALL DETAILS/NOTES AS REQUIRED. |
| 5-CLARIFY IF ENTRY DOOR IS GOING TO BE |
| THE MEANS OF EGRESS. PRODUCT APPROVAL |
| SUBMITTED IS FOR NON-IMPACT DOOR. NEED |
| DOOR W/ IMPACT GLAZING OR SOLID DOOR. |
| SEE NOTES ON DWG #2 AND CLARIFY. |
| 6-SPECIFY ROOF TILE FASTENERS AS REQ'D |
| BY SEC. 104.2.1.1 CITY AMENDMENTS TO |
| FBC AND SEC. 1606.3 FBC 2001. |