Plan Review Notes For Permit 04010955 |
Permit Number |
04010955 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-30 00:00:00 | DENIED: | | 2001 FBC(M) 601.4 EXCEPTION 1 THROUGH 3 | | | | RETURN AIR JUMPERS SHALL BE A MINIMUM | | OF 1 1/2 TIMES THE CROSS SECTIONAL AREA | | (SQ INCHES) OF THE SUPPLY DUCT SERVING | | THAT AREA.MASTER BEDROOM SHALL INCLUDE | | ALL SUPPLY AIR TO THE MASTER SUITE FOR | | THE TOTAL SUPPLY AIR TO THAT AREA. | | PLEASE SEE THE ATTACHED SCHEDULE TO | | REVISE PLANS AND RESUBMIT FOR APPROVAL. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|