Plan Review Notes
Plan Review Notes For Permit 04010955
Permit Number 04010955
Review Stop M
Sequence Number 1
Notes
Date Text
2004-01-30 00:00:00DENIED:
 2001 FBC(M) 601.4 EXCEPTION 1 THROUGH 3
  
 RETURN AIR JUMPERS SHALL BE A MINIMUM
 OF 1 1/2 TIMES THE CROSS SECTIONAL AREA
 (SQ INCHES) OF THE SUPPLY DUCT SERVING
 THAT AREA.MASTER BEDROOM SHALL INCLUDE
 ALL SUPPLY AIR TO THE MASTER SUITE FOR
 THE TOTAL SUPPLY AIR TO THAT AREA.
 PLEASE SEE THE ATTACHED SCHEDULE TO
 REVISE PLANS AND RESUBMIT FOR APPROVAL.
  